Function
TSL3-63B is a kind of circuit breaker with complete update of residual current detection based on current type A RCCB. It can not only effectively protect AC and pulsing DC (A type) the possible compound residual current (F type) but also smoothen DC and high frequency residual current (1KHz). In a circuit consisting of rectifier inverter frequency inverter etc. the leakage current caused in DC loop circuit can be effectively detected and protected.
Application
Industry medical EV charger elevator etc.
Standards
Conforms to standard: IEC/EN61008-1 IEC/EN62423
Detection Residual Current Type
AC + A + smoothing DC + F + high frequency signal (1KHz)
Specification
| Parameter | Value |
|---|---|
| Rated Voltage | 240V~ 1P+N 415V~ 3P+N |
| Rated Current | 16A 25A 32A 40A 63A |
| Rated Residual Operated Current | 0.03A 0.1A 0.3A |
| Poles | 1P+N 3P+N |
| Type of Residual Current | Type B (AC + A + smoothing DC + F + high frequency signal 1KHz) |
| Rated Limited Short Circuit Current | 10000A |
| Rated Making and Breaking Capacity | 1000A |
| Rated Residual Making and Breaking Capacity | 1000A |
| Rated Insulation Voltage | 1P+N: 250V 3P+N: 500V |
| Rated Impulse Withstand Voltage | 4000V |
| Electrical Life | 2000 times |
| Mechanical Life | 10000 times |
| Operating Ambient Temperature | -25? to +40? |
| Storage Ambient Temperature | -25? to +70? |
| Tightening Torque | 3 N·m |
| Connection Capacity | 16 mm² |
| Pollution Level | 2 |
| Protection Level | IP20 |